Código EAN8595057626171
Elcodigo aduanero73063041
Peso1.17 kg/m
Materialsteel
Tratamiento superficial
ZNM: Sendzimir Galvanized, zinc layer 15 - 27 micron, replaces primer, medium corrosion resistance - group - 2
Resistencia térmica-60 - 250 °C
Resistencia mecánica1250 N/5cm
Protección mecánicaIK10
Longitud3 m
Diámetro exterior37 mm
Diámetro interior (min.)34,4 mm
Funcionalidad en fuegoP15-R - P90-R, E30 - E90, PS15 - PS90
Tipo de manguitoP29
Código de clasificación44561
Corresponde a las normasČSN EN 61386-1 ed.2
Fire resistance standardsČSN 73 0895, DIN 4102-12, STN 92 0205
Max. load for fire resistance10 kg

The pipes are suitable for mechanical protection of conductors and cables. Threaded conduits are supplied with one coupler. While using pipes along with bushing 4813/P - 4842/P and 4913 - 4942 is scope of application only -5 - +60 °C.

Note for system with maintained functionality in fire:
max. 1 piece of cable in the pipe
You find more information in the catalogue Systems with maintained functionality in fire.